电线电缆网 > 电气装备用线缆 > kvvr和rvv的区别(完整版)
kvvr和rvv的区别 - 无图版
wgd99 --- 2010-12-29 16:24:53
1
客户要求rvv的护套电缆 结果我们库房只有kvvr的 库房的说没事 通用 对吗?高手指点
dlr111 --- 2010-12-29 16:33:36
2
wgd99 --- 2010-12-29 17:13:20
3
liujing81 --- 2010-12-29 20:35:36
4
BXY1985 --- 2010-12-31 13:38:53
5
RVV电压等级300/300V,KVVR电压等级450/750V,用户能正常使用。
mxsf1984 --- 2010-12-31 14:41:38
6
uclei --- 2010-12-31 20:43:26
7
用途不一样!
chenhaonan --- 2011-01-03 15:27:24
8
chenhaonan --- 2011-01-04 08:28:41
9
sanewcable --- 2011-01-04 10:46:31
10
aaa565 --- 2011-02-16 21:59:24
11
宝源电工 --- 2011-02-17 15:28:37
12
whcqbf --- 2011-03-16 16:35:37
13
loveyou --- 2011-03-18 11:15:56
14
RVV的护套应该是白色的把KVVR也是白色的啊
[loveyou 在 2011-3-18 20:55:52 编辑过]
819853348 --- 2011-03-24 12:45:20
15
wxw --- 2011-04-14 10:32:40
16
pzxyytf --- 2011-05-04 15:24:18
17
Aric --- 2011-05-04 15:56:30
18
学习。。
albert0829 --- 2011-08-08 18:37:39
19
[albert0829 在 2011-8-8 18:38:28 编辑过]
coolboys --- 2011-08-10 21:52:24
20
ludiyuanyi --- 2011-08-14 16:56:14
21
各位说了这么多,我阐述几点,据我所掌握的,RVV执行GB/T 5023.5-2008标准,应该有四种:
一、60227 IEC 52(RVV),额定电压300/300V,绝缘厚度0.5、0.75平方——0.5mm,绝缘线芯过1500V电压试验,成品过2000V电压试验。
二、60227 IEC 53(RVV),额定电压300/500V,绝缘厚度0.75、1.0平方——0.6mm,1.5平方——0..7mm,2.5平方——0..8mm,绝缘线芯绝缘厚度0.6mm过1500V电压试验,大于0.6mm过2000V电压试验,成品过2000V电压试验。
另外还有90度的耐热型的60227 IEC 56(RVV-90),60227 IEC 57(RVV-90)两种,和上面的两种在绝缘电阻,绝缘厚度等上面还是有点差别的,具体大家看标准规定。
而KVVR呢,执行标准GB/T 9330-2008,电压等级450/750V,绝缘厚度跟上面的RVV有的一样,有的不一样,而成品试验电压是3000V,RVV护套厚度是标准明确约定尺寸的,KVVR护套厚度应按计算的假定尺寸来确定,应该两者是有区别的。
由此可见,这两者是不可以通用的。电线电缆跟其他产品不一样,涉及安全啊,是不允许降级使用的。不要为了几个小钱做这样的事啊,兄弟。
[ludiyuanyi 在 2011-8-14 16:58:12 编辑过]