电线电缆网 > 通讯电缆 > ANSI/TIA/EIA-568-B.2导体要求?(完整版)

ANSI/TIA/EIA-568-B.2导体要求? - 无图版

kaka2004 --- 2009-03-31 11:06:05

1

4.3.2 Applicability
Horizontal cables shall consist of four balanced twisted-pairs of minimum 24 AWG thermoplastic
insulated solid conductors enclosed by a thermoplastic jacket. Bundled and hybrid cables may be
used for horizontal cabling in accordance with clause 4.3.6. Four-pair horizontal cables containing
conductor diameters larger than 24 AWG, up to and including 22 AWG, that meet or exceed the
requirements of this Standard may also be used.

请确认是否只是24-22AWG导体才能被用,达到或超出这个标准要求也可使用,这个是针对水平布线和骨干线。

那生产跳线在ANSI/TIA/EIA-568-B.2并没有要求其导体大小,26AWG是否可以使用?

kaka2004 --- 2009-03-31 11:22:33

2

是否只要达到ANNEX N的要求就行了?

wenli308 --- 2009-05-13 22:23:15

3

顶 

 

 

lsr66 --- 2009-05-13 23:13:00

4

当然可以用26#线,只要达到跳线标准就可以。
kaka2004 --- 2009-05-14 08:07:58

5

能确认有明文的规定吗?谢谢!

lsr66 --- 2009-05-14 08:50:54

6

严格来讲,如果要看到明文的规定,只有FTP线才可用26AWG,但实际上,客户是上帝啊,客户都许可了UTP线也用到26AWG,为什么还要墨守成规?

明文请参见:ANSI/TIA/EIA-568-B.1      6.4.1.4 小节。

jizhuan501 --- 2009-05-14 09:48:01

7

学习了!
kaka2004 --- 2009-05-14 09:58:06

8

我们用了好几年了26AWG UTP 铜规格,28AWG也有做,只不过是想证实一下规定而已,了却一个心愿。

sxq000888 --- 2009-05-14 17:53:15

9

按用户要求做吧,用户无要求按标准做总不会错的
wenli308 --- 2009-05-18 16:03:02

10

顶  学习了
aou83 --- 2009-07-01 18:32:52

11

可是26AWG的UTP可以符合Cat5e的規格嗎?

一直以爲24AWG會比較好!

YKTVA8 --- 2015-01-13 14:04:17

12

GOOD JOB!
ryu --- 2015-10-30 09:40:49

13

學習成長了<div>感謝!</div>
carey210 --- 2015-11-07 16:34:27

14

说真的,能满足客人的需求才是重要的,做得再好,没人要,也等于0
ryu --- 2015-11-09 17:25:04

15

如果是長鏈路 (50M)上 26AWG Cable 送ETL認證,會過不了唷!<div>但是短米數(10M以下)基本上在C5e是可以通過認證的</div><div>但最後還是客戶只要接受就可以了!