电线电缆网 > 电力电缆 > 假定直径算外护套厚度,求指导(完整版)
假定直径算外护套厚度,求指导 - 无图版
ybh202208 --- 2023-06-13 21:37:40
1
按照GB/T:12706.1-2020,附录1里面的介绍,算一下护套厚度,但是跟别人算出来有出入,望指导。下面是我的算法。
举例1:YJV-1kV-4*150
1.导体假设直径:查表得150假设直径=13.8mm
2.绝缘线芯假设直径:绝缘线芯假设直径=13.8+2*1.4=16.6mm
3.缆芯直径:4芯缆芯直径=2.42*16.6=40.172mm,修约=40.2mm
4.外护套厚度=0.035*40.2+1.0=2.407,修约=2.4
举例2:YJV22-1kV-4*150
1.导体假设直径:查表得150假设直径=13.8mm
2.绝缘线芯假设直径:绝缘线芯假设直径=13.8+2*1.4=16.6mm
3.缆芯直径:4芯缆芯直径=2.42*16.6=40.172mm,修约=40.2mm
4.内衬层:缆芯直径>40mm,内衬层=40.2+2*0.6=41.4mm
5.铠装层:铠装前外径为30-70之间,钢带厚度取0.5mm,铠装层=41.4+4*0.5=43.4mm
6.护套厚度:=0.035*43.4+1.0=2.519,修约=2.5mm
zhangyuhang564851702 --- 2023-06-14 07:43:18
2
绕包:
缆芯之后40.2+0.6*2+1.6附件垫层=43
铠装:43+0.5*4=45
护套=0.035*45+1=2.6
挤包:按你算的
psy --- 2023-06-14 08:00:28
3
weidong --- 2023-06-14 08:14:05
4
jirui123 --- 2023-06-14 09:36:47
5
812530915 --- 2023-06-14 09:39:31
6
PLWH --- 2023-06-14 09:55:13
7
楼主你的假定计算完全错了,需要仔细研究12706附录假定计算方法,并结合标准正文要求,揣摩每句话的含义。对于护层假定计算,无论有无内衬层,无论是挤包还是绕包内衬层,假定直径都要加上2*0.4或2*0.6。挤包内衬与绕包内衬的假定计算不同,绕包内衬还要考虑附加垫层引起的直径增加量1.0或1.6。YJV22-1kV 4*150(挤包内衬)护套标称厚度2.5,YJV22-1kV 4*150(绕包内衬)护套标称厚度2.6。
ybh202208 --- 2023-06-14 21:09:40
8
zhangyuhang564851702:例1:缆芯之后应为40.2+0.6*2=41.4 护套为0.035*41.4+1.0=2.4(修约)
例2:收线要确定你是绕包内衬层还是挤包
绕包:
缆芯之后40.2+0.6*2+1.6附件垫层=43
铠装:43+0.5*4=45
护套=0.035*45+1=2.6
挤包:按你算的
感谢指正
ybh202208 --- 2023-06-14 21:10:00
9
PLWH:楼主你的假定计算完全错了,需要仔细研究12706附录假定计算方法,并结合标准正文要求,揣摩每句话的含义。对于护层假定计算,无论有无内衬层,无论是挤包还是绕包内衬层,假定直径都要加上2*0.4或2*0.6。挤包内衬与绕包内衬的假定计算不同,绕包内衬还要考虑附加垫层引起的直径增加量1.0或1.6。YJV22-1kV 4*150(挤包内衬)护套标称厚度2.5,YJV22-1kV 4*150(绕包内衬)护套标称厚度2.6。
感谢指正
ybh202208 --- 2023-06-14 21:36:01
10
举例:YJV-8.7/15kV-3*300
1.导体假设直径:查表得300假设直径=19.5mm
2.绝缘线芯假设直径:绝缘线芯假设直径=19.5+2*4.5+3=31.5mm
3.金属屏蔽增加:金属屏蔽标称截面积=1*0.1*40=4mm,查表得增加值=0.5
绝缘线芯加增加值=31.5+0.5=32mm
4.缆芯直径:3芯缆芯直径=2.16*32=69.12mm,修约=69.1mm
5.内衬层:69.1+2*0.6=70.3mm
6.外护套厚度=0.035*70.3+1.0=3.4605,修约=3.5mm
举例:YJV22-8.7/15kV-3*300
1.导体假设直径:查表得300假设直径=19.5mm
2.绝缘线芯假设直径:绝缘线芯假设直径=19.5+2*4.5+3=31.5mm
3.金属屏蔽增加:金属屏蔽标称截面积=1*0.1*40=4mm,查表得增加值=0.5
故绝缘线芯加增加值=31.5+0.5=32mm
4.缆芯直径:3芯缆芯直径=2.16*32=69.12mm,修约=69.1mm
5.内衬层(隔离套):隔离套厚度=0.02*69.1+0.6=1.982,修约=2.0
隔离套外径=69.1+2*2.0=73.1mm
6.钢带:>70,厚度取0.8mm,钢带外径=73.1+4*0.8=76.3mm
6.外护套厚度=0.035*76.3+1.0=3.6705,修约=3.7mm
wzg196 --- 2023-06-14 21:43:27
11
402663419 --- 2023-06-15 07:44:28
12
ybh202208:我又算了一个中压电缆的,各位大佬再帮我看看是否正确,
举例:YJV-8.7/15kV-3*300
1.导体假设直径:查表得300假设直径=19.5mm
2.绝缘线芯假设直径:绝缘线芯假设直径=19.5+2*4.5+3=31.5mm
3.金属屏蔽增加:金属屏蔽标称截面积=1*0.1*40=4mm,查表得增加值=0.5
绝缘线芯加增加值=31.5+0.5=32mm
4.缆芯直径:3芯缆芯直径=2.16*32=69.12mm,修约=69.1mm
5.内衬层:69.1+2*0.6=70.3mm
6.外护套厚度=0.035*70.3+1.0=3.4605,修约=3.5mm
举例:YJV22-8.7/15kV-3*300
1.导体假设直径:查表得300假设直径=19.5mm
2.绝缘线芯假设直径:绝缘线芯假设直径=19.5+2*4.5+3=31.5mm
3.金属屏蔽增加:金属屏蔽标称截面积=1*0.1*40=4mm,查表得增加值=0.5
故绝缘线芯加增加值=31.5+0.5=32mm
4.缆芯直径:3芯缆芯直径=2.16*32=69.12mm,修约=69.1mm
5.内衬层(隔离套):隔离套厚度=0.02*69.1+0.6=1.982,修约=2.0
隔离套外径=69.1+2*2.0=73.1mm
6.钢带:>70,厚度取0.8mm,钢带外径=73.1+4*0.8=76.3mm
6.外护套厚度=0.035*76.3+1.0=3.6705,修约=3.7mm
对的。YJV-8.7/15kV-3*300的内衬层是计算用,实际生产不需要。
Ericzll --- 2023-06-15 09:45:14
13
匿名 --- 2023-06-15 10:33:03
14
666
snow623009043 --- 2023-06-25 09:35:21
15
jinfeng --- 2024-03-13 16:31:45
16
snow623009043:紧压导体,导体外径差不多是:14.5mm
你这个的原理可以说一下吗?