| APPLIANCE WIRING MATERIAL |  |
| Subj.758 | Section 1 | Page 10455 | Issued:1999-10-29 |
| Revised:2012-08-24 |
| Style 10455 | Single Conductor Cable with Extruded Non-integral Jacket. |
|
| Rating | 90 deg C, 600 Vac, Cable flame. |
|
| Conductor | 30 AWG min. solid or stranded round. |
|
| Insulation | Labeled or complying with Manufacturer's AWM Procedure. |
|
| Shield | Optional. |
|
| Covering | Optional. A barrier layer if employed, may be a fibrous wrap, serving or braid; Paper; Nylon: oriented Polyethylene terephthalate; or a thermoplastic tape wrap. |
|
| Jacket | Extruded PVC |
| dia in inches of 0.700 or less | 30 mils min average | 24 mils minimum at any point |
| 1.000 dia or less | 45 avg | 36 min |
| 1.001-1.500 dia | 60 avg | 48 min |
| 1.501-2.500 dia | 80 avg | 64 min |
| 2.501-4.00 dia | 110 avg | 88 min |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | Internal wiring or external wiring. |
|
UL and the UL Logo are trademarks of UL LLC © 2013