电线电缆网 > 电力电缆 > 各位厂家35kV交联电缆耐压试验电压是多少?(完整版)

各位厂家35kV交联电缆耐压试验电压是多少? - 无图版

PLWH --- 2007-12-20 20:18:53

1

请教各位,各厂家目前35kV交联电缆耐压试验按多高电压?65kV/5min还是65kV/30min或91kV/5min?

[PLWH 在 2007-12-20 20:20:37 编辑过]

xue8853 --- 2007-12-20 20:20:17

2

91kV/5min
飞刀 --- 2007-12-20 22:57:58

3

GB/T12706-2002标准有明确规定
PLWH --- 2007-12-21 10:55:47

4

标准我知道,91kV/5min或65kV/30min,我想知道多数厂家都是严格按GB/T 12706-2002做的吗?

ma800722 --- 2007-12-21 15:39:18

5

65kV/30min
wangsf1979 --- 2007-12-23 22:35:35

6

65KV/30min 或91KV/5min 都可以,看你试验设备承受的能力二都选一.

至少我们公司是严格按照国家标准做的.

一叶孤舟 --- 2007-12-24 19:59:30

7

65KV/30min 或91KV/5min 都可以,GB/T 12706-2002有严格规定
dymlyj --- 2007-12-26 11:01:33

8

65kV/30min这是我们家经常用到的阿!

 

jun --- 2007-12-26 11:08:06

9

65KV/30min 或91KV/5min 都可以,看你试验设备承受的能力二选一.
xujun878 --- 2007-12-26 17:42:07

10

我们厂一般就用91KV/5min 的
ls518 --- 2007-12-26 20:44:16

11

65kV/30min,我们是经常打的,91KV/5min 我们很少打了啊,
晓叶 --- 2007-12-26 22:51:12

12

严格按GB/T 12706-2002   65kV/30min    
SODDY6387 --- 2007-12-29 22:58:28

13

65kv/30Min是国家老标准,91kv/5Min是新标准。打91kv高压油杯的头很难作。
YZCYJ --- 2007-12-30 10:40:43

14

我们也是65kv/30Min,以前也用过91的,打坏了几个油杯!

飞刀 --- 2007-12-30 11:27:28

15

按标准做,另外还要看你的设备能力
haimooo --- 2007-12-30 17:46:57

16

设备局限性,65kv/30min

xuesong --- 2007-12-30 20:45:36

17

65kV/5min  ?你也太敢想了
快乐天使 --- 2008-01-01 11:25:06

18

65kv/30min   严格按国标执行

fyc8 --- 2008-01-02 21:46:25

19

建议楼主严格按国家标准去进行试验,如果不能按照标准进行例行试验,一旦电缆存在缺陷就不能及时发现了,到时真的是后患无穷呢.现在不少电缆企业由于采购的局放设备是老的设备,只能进行65/30min耐压试验.按91kv/5min进行耐压试验,对电缆头的做头要求比较高呢,另变压器油也要质量比较好的,否则头端容易发生击穿的.

nongheng --- 2008-01-04 13:48:04

20

我觉得这两个标准都差不多,要联系实际进行测试就行拉,
QC --- 2008-01-07 16:55:17

21

我们用65kv/30Min ,     91kv/5Min对电缆本体有一定的伤害,并且终端处理不好,在外屏1cm左右容易击穿,和击穿油杯.

 

PLWH --- 2008-01-16 16:29:00

22

若接到大批量生产订单时,交货期很紧,采用65kV/30min方法试验,30min打一根绝缘线芯,从半成品到成品,一段3芯的交联电缆仅打耐压就需要3小时,从交货期角度考虑,似乎时间长了些。所以打65kV/30min不如打91kV/5min。

zhangluo --- 2008-01-27 13:13:23

23

91kv/5min快,适合产量大和设备允许的企业,

35kv头难做主要是局放问题,

电缆端头加均压环可明显改善试验质量

jydl --- 2008-01-28 14:32:43

24

一般情况下是91kv/5Min,主要聂决于你的局放设备是否能满足要求
hbszjly --- 2008-01-29 03:16:47

25

按GB T/16999   2005-35 应该是91KV/MIN

guying8 --- 2008-02-08 11:34:10

26

都是按照GB 12706做啊!到现在不知道有那个电缆厂自己弄!一个是耐压试验,一个是局部放电实验!!这个还不简单

shy --- 2008-02-13 21:01:58

27

1、35kV是指线电压,耐压试验电压我记得GB12706.2-2002标准要求是3.5*U0(U0指相电压),耐压试验电压值选择应首先搞清楚U0是多少。

2、5min耐压试验电压GB12706-2002标准我记得比GB12706-91标准提高了试验电压,老标准是2.5U0

3、耐压试验电压值应执行最新标准要求规定;如能确认延长时间至30min并相应降低试验电压值,试验结果是等效的,我认为也可以,毕竟耐压试验的目的是用来发现电缆绝缘中可能存在的严重缺陷(包括材料缺陷、工艺缺陷等问题)

wxchen --- 2008-02-14 10:34:13

28

91/5

 

chb8899 --- 2008-02-22 14:29:21

29

65KV/30min 或91KV/5min 都可以,GB/T 12706-2002有严格规定
skyj --- 2008-02-27 08:33:02

30

65kv/30Min 好做,91kv/5Min有点难度,我们一般是做65kv/30Min ,91kv/5Min很少做,油杯很容易击穿
zhqpxt --- 2008-03-06 14:12:30

31

91KV/5min 可以使用硅胶高压成品端头试试!PASS
叶儿 --- 2009-08-19 11:12:05

32

65kV/30min
563410548 --- 2009-08-23 09:41:40

33

65KV/30min 或91KV/5min 都可以
ll88588 --- 2009-08-27 17:25:37

34

行业内可能更多采取65KV/30min标准做试验,91KV电压太高,对终端要求太高,极易把油杯打坏。
火焰山 --- 2009-08-30 19:51:49

35

65kv/30Min是国家老标准,91kv/5Min是新标准,我们厂一般就用91KV/5min 的
huada --- 2009-09-04 21:21:39

36

65kv,30分钟
王武 --- 2009-09-06 08:45:35

37

12706标准规定2.5U0----30min,         3.5U0----5min   两个任选         

试验之前请确认 是21/35KV还是26/35KV                          前者 53KV/30min 或73,5KV/5min后者65KV/30min 或91KV/5min

 

叶儿 --- 2009-09-13 16:10:57

38

65KV/30min
dtdtxy --- 2009-09-21 16:07:16

39

除非购买方另有要求, 制造方可任选以下程序进行例行电压实验:

3.5U0,5min;

2.5U0,30min.

yhshk --- 2009-09-21 18:14:59

40

91KV/5min
icyspring --- 2009-09-26 13:01:27

41

65KV/30min

 

coastal --- 2009-10-04 13:24:48

42

PLWH:
请教各位,各厂家目前35kV交联电缆耐压试验按多高电压?65kV/5min还是65kV/30min或91kV/5min?

[PLWH 在 2007-12-20 20:20:37 编辑过]

 

这个看您们公司的实验设备了。

whw1678 --- 2009-10-05 13:30:51

43

91KV/5MIN
zyhwainia --- 2009-10-12 12:26:33

44

GB/T12706-2002标准有明确规定
快棋手 --- 2009-10-13 13:36:31

45

65kV/30min或91kV/5min两种都要做
tlxjz --- 2009-10-14 15:13:31

46

65KV/30min 或91KV/5min 都可以,GB/T 12706-2002有严格规定

但是大多数厂家都首选65KV/30min ,这种对电缆和试验设备都有好处,电压冲击小。

fangteng1 --- 2011-07-19 21:43:35

47

65kV/30min,我们是经常打的,91KV/5min 我们很少打了啊
ping123 --- 2011-12-06 13:54:20

48

基本上多是65KV/30min
srt0801 --- 2011-12-19 16:32:57

49

65kV/30min
chentong02 --- 2011-12-20 11:43:20

50

学习一下
clp521 --- 2011-12-20 14:44:14

51

65KV/30min 或91KV/5min 都可以,一般都是采用65千伏30分钟,91千伏5分钟风险有点大,容易端头击穿
DWF --- 2011-12-23 12:01:22

52

40.5/1小时
ying696000 --- 2012-03-30 10:09:59

53

sunmnmn --- 2012-06-26 14:26:25

54

65kV/5min和9165kV/5min都可以
秦冬利 --- 2012-06-28 16:16:48

55

标准上有的

fyc8 --- 2017-06-23 09:34:26

56

不知大家想过这个问题没有?根据标准有二种,一是3.5U0  5分钟;二是2.5U0 30分钟,第一种打耐压难度较大;第二种耐压时间太长。如果将耐压值定为3U0,按照等效的原理,不知道耐压时间要多长?
fyc8 --- 2017-06-23 09:44:34

57

也不是我瞎想出来的,当初国标12706-2002修订的时候,只有一种规定:3.5U0  5min。后不少代表纷纷提出,国内的不少局放进口设备,当时的高压电压根本达不到91kV,如果就按此规定,进口的局放设备就要报废。后由上缆所国标起草人员蒋佩兰,提出了2.5U0,30min第二种方法,为了说明与第一种方法等效,用了半天的时间向与会人员用理论公式来证明的。不过大部分人员听不懂的,用的理论公式有点高深的。我当时也未听的懂。呵呵!
lp34623829 --- 2017-09-01 20:48:20

58

65kV/30min,同上,。91kv 的设备和油杯都是你不稳定因素
512141753 --- 2018-09-04 09:42:28

59

出厂是91kv/5Min
-- 结束 --